Fuse Size Calculator
Size fuses correctly for PV strings, battery banks, and inverter circuits — with NEC 690 compliant recommendations.
How to Use This Calculator
Enter max circuit current and wire gauge
Input the maximum continuous current in amps and the AWG size of the wire being protected. The fuse must protect the wire — it must blow at a current below the wire's ampacity. If the fuse is larger than the wire can safely carry, the wire becomes the fuse (and a fire hazard).
Select circuit type
Different solar circuits use different NEC 690 sizing rules. PV string fuses use a 156% multiplier (125% × 125% as required by NEC 690.8). Battery and load circuits use 125%. The circuit type also determines the recommended fuse style — DC-rated fuses for PV strings, ANL for battery banks.
The fuse type matters as much as the rating
A standard AC fuse in a DC circuit is a fire hazard — DC arcs don't self-extinguish the way AC arcs do. Always use DC-rated fuses and breakers in any solar DC circuit. Look for a DC voltage rating equal to or greater than your system voltage.
The Formula
The fundamental rule: the fuse protects the wire, not the load. A fuse sized to protect a load (say, exactly the load's rated watts) may be larger than the wire can safely carry. Always size the fuse to the wire first, then verify the wire is large enough for the load.
Example
PV string fuse — 300W panel with 10 AWG wire
A 300W panel has Isc of 8.5A. It's wired with 10 AWG wire (ampacity: 35A). What fuse is needed at the combiner box?
Result
A 15A DC-rated fuse is correct. An AC-rated 15A fuse in this circuit is a code violation and potentially dangerous — DC arcs at 48V+ won't extinguish in an AC fuse.