Solar Wire Size Calculator
Find the right AWG wire gauge for your solar system. Covers DC and AC circuits with a full comparison table showing voltage drop and power loss for every gauge.
| AWG | Ampacity | Drop V | Drop % | Loss W |
|---|---|---|---|---|
| 14 | 15A | 1.52V | 6.31% | 30.3W |
| ► 12 | 20A | 0.95V | 3.97% | 19.1W |
| 10 | 30A | 0.60V | 2.50% | 12.0W |
| 8 | 40A | 0.38V | 1.57% | 7.5W |
| 6 | 55A | 0.24V | 0.99% | 4.7W |
| 4 | 70A | 0.15V | 0.62% | 3.0W |
| 2 | 95A | 0.09V | 0.39% | 1.9W |
| 1 | 110A | 0.07V | 0.31% | 1.5W |
| 1/0 | 125A | 0.06V | 0.25% | 1.2W |
| 2/0 | 145A | 0.05V | 0.19% | 0.9W |
| 3/0 | 165A | 0.04V | 0.15% | 0.7W |
| 4/0 | 195A | 0.03V | 0.12% | 0.6W |
How to Use This Calculator
Enter the current in amps
Use the actual current that will flow through the wire. For solar applications: panel-to-controller runs use panel Isc × 1.25 (NEC 125% safety factor). Battery-to-inverter cables use inverter rated watts ÷ battery voltage. For branch circuits, use the load's rated current × 1.25.
Enter the one-way distance
Measure the one-way distance from source to load. The calculator automatically doubles this to account for both the positive and negative conductors (the return path). In a 24V system, the negative cable carries the same current as the positive — both must be sized correctly.
Set system voltage and max voltage drop
Lower voltages are more sensitive to voltage drop. A 1V drop on a 12V system is 8.3% — on a 240V system it's 0.4%. The NEC recommends 3% maximum for branch circuits. For solar systems, use 1-2% for critical runs (battery bank to inverter, high-current DC runs) and up to 5% for less critical runs (panel combiner to charge controller).
Read the AWG table
The results table shows every AWG size, its ampacity rating, calculated voltage drop, and power loss for your specific circuit. The recommended wire is highlighted. Going one size larger than the minimum is inexpensive and reduces power loss noticeably — worth considering for permanent installations.
The Formula
Copper resistivity values (ohms per 1,000 feet at 75°C) come from standard AWG tables. The calculator uses NEC Table 9 values for stranded copper conductors — the same table electricians use for code compliance.
Quick AWG Reference
Example
Battery to inverter cable — 24V, 2,000W system
A 2,000W inverter on a 24V battery bank draws up to 2,000 ÷ 24 = 83A DC. The inverter is 8 feet from the battery bank (one-way).
AWG 2/0 handles the 83A load within the 2% drop target for a short 8-foot run. Using AWG 1/0 (125A rated) would give 0.13V drop at 0.54% — slightly over the 2% target but still below 3%. For this critical high-current run, AWG 2/0 is the right choice — the cost difference is minimal but the efficiency gain is real.