AWG to mm² Calculator

Convert American Wire Gauge (AWG) to metric mm² and back. Includes full table with diameter, resistance, and ampacity for every gauge.

Wire specifications
10 AWG = 5.26 mm²
Diameter2.59 mm
Resistance3.280 mΩ/m
Ampacity (free air)55 A
Ampacity (conduit)35 A
AWGmm²Diam (mm)Res (mΩ/m)Amp (free)Amp (conduit)
4/0 (0000)107.211.680.161360230
3/0 (000)8510.40.203302200
2/0 (00)67.49.270.256265175
1/0 (0)53.58.250.323230150
142.47.350.407195130
233.66.540.513170115
326.75.830.647145100
421.15.190.81512585
613.34.111.30010165
88.373.262.0607350
105.262.593.2805535
123.312.055.2104125
142.081.638.2803220
161.311.2913.1602213
180.8231.0220.9301610
200.5180.81233.280117
220.3260.64452.94075
240.2050.51184.2003.53
260.1290.405133.9002.22
280.0810.321212.9000.830.7
300.05090.255338.6000.520.5
Link copied to clipboard

How to Use This Calculator

Choose conversion direction

Select AWG → mm² to look up a US wire gauge, or mm² → AWG to find the closest AWG equivalent for a metric wire size. The AWG direction shows exact specifications; the mm² direction finds the nearest standard AWG gauge.

Select or enter your gauge

For AWG mode, select the gauge from the dropdown (4/0 to 30). For mm² mode, enter the cross-sectional area in square millimeters — common IEC values are 1.5, 2.5, 4, 6, 10, 16 mm². The calculator finds the closest AWG equivalent.

Read the specifications

Results show the wire's cross-sectional area, diameter, resistance per meter, and ampacity — both in free air and in conduit. Use the full reference table below the calculator to compare multiple gauges side-by-side.

AWG vs mm² Explained

American Wire Gauge (AWG) is the US standard for wire sizing. The AWG number is inversely proportional to wire size — lower AWG number means thicker wire. The scale runs from 4/0 (0000) as the thickest common residential wire down to 30 AWG for fine signal wire.

The IEC (International Electrotechnical Commission) standard used in Europe, Australia, and most of the world specifies wire by cross-sectional area in mm². Higher mm² numbers mean thicker wire — the opposite of AWG convention.

AWG to mm² (approximate): mm² = 0.012668 × 92^((36-AWG)/19.5) Diameter from AWG: d (mm) = 0.127 × 92^((36-AWG)/39) Resistance: R = resistivity (ρ) ÷ cross-section area (copper: ρ = 1.72 × 10&sup8; Ω·m at 20°C)

Example

Sizing wire for a 3,000W solar inverter at 48V DC

A 3,000W inverter at 48V draws 62.5A (3,000 ÷ 48). You need wire that handles at least 62.5A with a safety margin. NEC recommends sizing at 125% for continuous loads: 62.5 × 1.25 = 78.1A minimum.

Required current78.1 A minimum
Looking up AWG table4 AWG = 85A (free air)
AWG 4 cross-section21.1 mm²
EU equivalent25 mm² (next standard size)

4 AWG (21.1 mm²) is the minimum for free-air installations. If the wire runs through conduit with other wires, you'd need to derate — in that case, use 2 AWG (33.6 mm²) or the EU 35 mm² equivalent.

FAQ

AWG was originally a measure of how many times a wire was drawn through a die during manufacturing. More draws = thinner wire = higher gauge number. So 10 AWG wire has been drawn more times than 4 AWG, making it thinner. The system is counterintuitive but deeply entrenched in US electrical practice. Remember: in AWG, smaller number = bigger wire.
For residential solar: panel-to-combiner box typically uses 10 or 12 AWG PV wire. Combiner to charge controller or inverter uses 4-8 AWG depending on current. Battery bank cables use 2/0 to 4/0 AWG for high-current DC runs. AC output from inverter to main panel uses 6-10 AWG. Always calculate the actual current (watts ÷ volts), apply the 125% NEC safety factor, and check the table for the minimum adequate gauge.
Free air ampacity assumes the wire is exposed with air circulating around it for cooling. Conduit (enclosed) ampacity is lower because heat builds up in the conduit, especially when multiple wires run together. The NEC requires derating for conduit installations: typically 70-80% of free-air ratings when 4+ current-carrying conductors share a conduit. For solar installations, always use the conduit column if the wire runs through any enclosed raceway.
Yes, with care. NEC 2020 now explicitly permits metric wire sizes. The key is to use the closest-sized or larger metric equivalent. For example, if you need 10 AWG (5.26 mm²), the nearest standard metric size is 6 mm² (slightly larger, slightly safer). Never use a smaller metric size as a substitute for a specified AWG gauge. Check your local authority having jurisdiction (AHJ) for any local requirements.

Related Calculators