Conduit Size Calculator
What size conduit do you need? Enter wire count, gauge, and type — get NEC-compliant minimum conduit size and fill percentage table.
| Size | Internal Area | Fill % | Status |
|---|---|---|---|
| 1/2" | 0.304 in² | 20.8% | ✓ Recommended |
| 3/4" | 0.533 in² | 11.9% | Fits |
| 1" | 0.864 in² | 7.3% | Fits |
| 1-1/4" | 1.496 in² | 4.2% | Fits |
| 1-1/2" | 2.036 in² | 3.1% | Fits |
| 2" | 3.356 in² | 1.9% | Fits |
| 2-1/2" | 5.858 in² | 1.1% | Fits |
| 3" | 8.846 in² | 0.7% | Fits |
| 4" | 15.904 in² | 0.4% | Fits |
How to Use This Calculator
Enter wire count and gauge
Enter the total number of conductors you're running in the conduit. For a standard 120V circuit: 2 wires. For 240V: 3 wires (2 hots + ground or neutral). For a solar PV string to a combiner box: typically 2 wires. Ground wires count toward conduit fill but NOT toward the ampacity derating that applies when more than 3 current-carrying conductors share a conduit.
Select wire type and conduit type
Choose your wire insulation type — THWN-2 is standard for most conduit runs; USE-2 for outdoor solar PV runs. The wire type affects insulation thickness and thus cross-sectional area. For conduit, select EMT (indoor), PVC (underground), or rigid metal (outdoor exposed).
Read the fill table
The results show the recommended minimum conduit size and a full table of all standard sizes with fill percentages. The highlighted row is the recommended size — use the next size up if you want room for future wiring additions.
The Formula
The NEC fill limits protect wires from heat buildup (high fill restricts airflow) and prevent physical damage during installation (pulling wires through an overfilled conduit can damage insulation). The 40% limit for 3+ conductors is the most common case in solar installations.
Example
Solar inverter AC output — 3 conductors of 10 AWG THWN-2 in EMT
Running 3 conductors of 10 AWG THWN-2 from a solar inverter to the main panel in EMT conduit. What size conduit is needed?
Result
A 1/2" EMT conduit is sufficient for 3 conductors of 10 AWG THWN-2 at only 20.8% fill — well under the 40% limit. If you need to add a 4th conductor later, you'd still fit — 4 × 0.0211 = 0.0844 in², which is 27.8% of 0.304 = still under 40%. To future-proof, installing 3/4" EMT gives you room for 6-8 conductors of this size.